In order to save the wasted power of underutilized, over-size ordinary UPS, and obtain “N+1” redundancy to ensure the critical system has high power availability, data centers now choose modular UPS as their first choice for critical power protection. With compact size, high efficiency and easy expansion according to power requirements. Modular UPS systems are growing fast in the three-phase market.
The HPM series is a modular uninterruptible power supply (UPS) for medium – and large-sized data centers. It features high efficiency (96%) and a high input factor of 0.99, minimizing UPS energy consumption. The modular design and the N+X parallel redundancy technology, making the expansion & management easier as well as reduce initial acquisition costs.
It supports hot-swappable and reduces the maintenance time to 5 minutes and improves system availability. The maximum capacity can be expanded to 1000KVA according to future needs, helping to lower initial investment.
General Features
- Adopting digital control design, and the control system is more reliable
- High input factor 0.99 and output factor 1.
- 3-level topology design, efficiency is up to 96%
- Support parallel expansion for cabinet, and parallel expansion is up to 4-6 cabinets.
- Batteries number of each group can be selected from 30 pieces to 50 pieces.
- With 7 inches (standard) and 10 inches (optional) colorful touch LCD screen
Technical Specifications
Module Model | HPM3300E-RM-40 | HPM3300E-RM-50 | |
Cabinet Model | HPM3300E-200/320/400 | HPM3300E-200/300/400/500/600/800/1000 | |
Cabinet capacity (VA) | 200k~400k | 200k~1000k | |
Module capacity (VA) | 40k | 50k | |
Max. Number | 05/8/10 | 4/6/8/10/12/16/20 | |
INPUT | |||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | ||
Operating voltage range | 138~305Vacfor 40% Load; 305~485Vac for 100% Load; | ||
Operating frequency range | 40Hz-70Hz | ||
Power factor | ≥0.99 | ||
Harmonic distortion (THDi) | ≤3% (100% linear load) | ||
Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) |
||
Bypass Frequency range | Frequency protection range: ±10% | ||
Power Walk In | Support | ||
Generator input | Support | ||
OUTPUT | |||
Rated voltage | 380/400/415Vac, (3Ph+N+PE) | ||
Power factor | 1 | ||
Voltage regulation | ±1% | ||
Output frequency | Line Mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | |
Bat. Mode | (50/60±0.1%)Hz | ||
Crest factor | 0.125694444 | ||
Harmonic distortion (THDv) | ≤1% with linear load; ≤3% with nonlinear load | ||
Efficiency | up to 96% |
BATTERY | |||||||
Battery voltage | Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8) |
||||||
Power module charge current | 20A (Max.) | ||||||
SYSTEM FEATURES | |||||||
Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | ||||||
Overload | Line Mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. | |||||
Bypass Mode | 135% overload for long term; >1000% overload for 100 ms | ||||||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | ||||||
Low battery voltage | Alarm and Switch off | ||||||
Self-diagnostics | Upon Power On and Software Control | ||||||
Backfeed | Support | ||||||
EPO | Shut down UPS immediately (turn to bypass optional) | ||||||
Battery | Advanced Battery Management | ||||||
Noise suppression | Complies with EN62040-3 | ||||||
Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | ||||||
Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | ||||||
ENVIRONMENTAL | |||||||
Operating temperature | 0℃~40℃ | ||||||
Storage temperature | -25℃~55℃ | ||||||
Humidity range | 0~95% (non condensing) | ||||||
Altitude | <1500m, derating required when >1500m | ||||||
Noise level(from 1M distance) | <68dB | <73dB | |||||
PHYSICAL | |||||||
Dimension WxD×H (mm) | UPS cabinet (S / F) |
200/320kVA: 600×850×2000 400kVA: 1200×850×2000 |
200/300/400kVA: 600×850×2000 | ||||
Power module | 440×620×130 | ||||||
Net weight (kg) | UPS cabinet (S / F) |
210~460 | 200kVA: 240; 300kVA: 260; 400kVA: 290; 500kVA: 480; 600kVA: 540; 800kVA: 960; 1000kVA: 1050 |
||||
Power module | 33 | 34 | |||||
STANDARDS | |||||||
Safety | IEC/EN62040-1, IEC/EN62477-1 | ||||||
EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) |