UB series power supply adopts online double conversion design and digital control technology and it features high input and output power factor(0.9). With ECO mode for energy-saving, intelligent battery management and excellent network management, it is a cost-effetive power solution for your critical devices. When UPS is on battery mode, it can shut down unnecessary load and extend the backup time of the critical load.
General Features
- True double-conversion
- Digital control guarantees high reliability
- ECO mode operation for energy saving
- Output receptacle control for non-critical load shedding capability
- Emergency power off function(EPO)
- Generator compatible
- Communications: RS-232,USB,SNMP card(Optional), Relay card (Optional)
- Bypass can be used when UPS is off (Settled in LCD)
- Cold start
Technical Specification
MODEL | UB 10-24 |
UB 10L |
UB 20-96 |
UB 20L |
UB 30-96 |
UB 30L-96 |
|||
Capacity (VA/Watts) |
1000VA/900W | 2000VA/1800W | 3000VA/2700W | ||||||
INPUT | |||||||||
Nominal Voltage |
208/ 220/230/240Vac(L+N+PE) | ||||||||
Operating Voltage Range |
110~300Vac @(0~60%) Load;120~300Vac @(60~70%)Load,140~300Vac @(70~80%)Load; 160~300Vac @(80~100%)Load |
||||||||
Operating Frequency Range |
50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing | ||||||||
Power Factor | > 0.85@25%Load;>0.95 @50%Load;>0.97@75%Load;>0.99 @ Nominal voltage& 100%Load | ||||||||
OUTPUT | |||||||||
Output Voltage | 208/220/230/240Vac:230Vac(Default) | ||||||||
Power Factor | 0.9 | ||||||||
Voltage Regulation |
±1% | ||||||||
Frequency | Synchronized Range |
45-55Hz ±0.02Hz@ 50Hz, 55-65Hz ±0.02Hz@60Hz | |||||||
Battery Mode &None Synchronized Range |
(50/60±0.02)Hz | ||||||||
Crest Factor | 3:1 | ||||||||
Harmonic Distortion (THDv) |
≤3% with linear load | ||||||||
≤5% with non-linear load | |||||||||
Waveform | Pure Sinewave | ||||||||
Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 4ms(Typical) | ||||||||
EFFICIENCY | |||||||||
ECO Mode | >93% | >94% | |||||||
BATTERY | |||||||||
Protect | Over-voltage(14.7v) /Low-voltage(10v) | ||||||||
PROTECTION | |||||||||
Overload Capacity |
Line Mode | 105%-150%, 30s turn to bypass mode ; >150% 300ms turn to bypass mode | |||||||
Battery Mode | 105%-150%, exceed 30s shutdown ; >150% exceed 300ms shutdown | ||||||||
INDICATORS | |||||||||
LED & LCD Display | Load/Battery/Input/Output/Operating Mode Information | ||||||||
ALARM | |||||||||
Battery Mode | Sounding every 4 seconds | ||||||||
Battery Low | Sounding every second | ||||||||
Overload | Sounding every 0.5 second | ||||||||
Fault | Continuously Sounding | ||||||||
MANAGEMENT | |||||||||
Smart RS-232/USB (Preferential) |
External Modbus card supported by RS232,Software supports Windows Family,Linux,FreeBSD | ||||||||
Intelligent Slot | SNMP (Standard or mini) independent to RS-232(Optional) | ||||||||
ENVIRONMENT | |||||||||
Operating Temperature |
0℃~40℃ | ||||||||
Humidity Range | 0~95% (Non-condensing) | ||||||||
Altitude | < 1500m | ||||||||
Noise Level | <50dB@ 1Meter |
PHYSICAL | ||
Dimension W×D×H (mm) |
144×400×215 | 191×468×337 |
STANDARDS | ||
Safety | IEC/EN62040-1 | |
EMC | IEC/EN62040-2 |